range |
ComPact
|
|
---|---|---|
product name |
ComPact NSXm
|
|
range of product |
ComPact NSXm
|
|
device short name |
NSXm 32N
|
|
product or component type |
Circuit breaker
|
|
device application |
Protection
Distribution |
|
Number of poles |
4P
|
|
protected poles description |
4d
|
|
neutral position |
Left
|
|
[In] rated current |
32 A at 40 °C
|
|
[Ue] rated operational voltage |
690 V AC 50/60 Hz
|
|
network type |
AC
|
|
network frequency |
50/60 Hz
|
|
suitability for isolation |
Yes conforming to EN/IEC 60947-2
|
|
utilisation category |
Category A
|
|
[Icu] rated ultimate short-circuit breaking capacity |
90 kA Icu at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 380…415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 600…690 V AC 50/60 Hz conforming to IEC 60947-2 |
|
Performance level |
N 50 kA 415 V AC
|
|
trip unit name |
TM-D
|
|
trip unit technology |
Thermal-magnetic
|
|
trip unit protection functions |
LI
|
|
control type |
Toggle
|
|
Circuit breaker mounting mode |
By screws
Clip-on |