range |
TeSys
|
|
---|---|---|
product name |
TeSys GV4
|
|
device short name |
GV4PEM
|
|
product or component type |
Multifunction circuit breaker
|
|
device application |
Motor protection
|
|
protection type |
Overload
Phase loss Ground fault protection Jam Short-circuit Short time short-circuit protection Locked rotor Phase unbalance Long start |
|
utilisation category |
Category A
|
|
suitability for isolation |
Yes conforming to IEC 60947-1
|
|
poles description |
3P
|
|
[Ue] rated operational voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
[In] rated current |
25 A
|
|
trip unit technology |
Electronic
Thermal-magnetic |
|
magnetic tripping current |
425 A
|
|
[Isd] short-time pick-up adjustment range |
5…13 x Ir
|
|
thermal protection adjustment range |
10…25 A
|
|
motor tripping class |
10
20 |
|
phase failure sensitivity |
Yes conforming to IEC 60947-4-1
|
|
breaking capacity |
Icu 100 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
Icu 50 kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2 Icu 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 Icu 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 208Y/120 V AC 50/60 Hz conforming to UL 60947 65 kA at 240 V AC 50/60 Hz conforming to UL 60947 35 kA at 480Y/277 V AC 50/60 Hz conforming to UL 60947 Icu 8 kA at 660…690 V AC 50/60 Hz conforming to IEC 60947-2 Icu 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 18 kA at 600Y/347 V AC 50/60 Hz conforming to UL 60947 |
|
[Ics] rated service breaking capacity |
100 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 2 kA at 660…690 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Uimp] rated impulse withstand voltage |
IEC 60947-2 8 kV
|
|
[Ui] rated insulation voltage |
800 V conforming to IEC 60947-2
|
|
mechanical durability |
40000 cycles
|
|
electrical durability |
40000 cycles for AC-3 at 440 V In/2
20000 cycles for AC-3 at 440 V In |
Schneider GV4PEM-25N TeSys Dijital Motor Koruma Şalter Çözümleri
Kategoriler: Genel, Motor Koruma Şalterleri, Motor Yol Verme Çözümleri, Tüm Ürünler
Etiketler: adana, aydin, beyaz, corlu, dijital, Edirne, gaziantep, gv4, gv4pem-25n, Istanbul, izmir, kesme(50kA), koruma, manisa, manyetik, motor, motorkoruma, şalter, schneider, Schneider electric, schneider-gv4, schneider-tesys, termik, termik(10-25a), tesys, urfa
Açıklama
Ek bilgi
Markalar | Schneider |
---|
Genel Bilgi
Güncellenecektir..
İlgili ürünler
Schneider 9001-KA2 Kontak Çözümleri
Ürün serisi Harmony 9001K Ürün ya da bileşen tipi Korumalı terminallerle kontak bloğu Ürün grubu 9001K
Schneider 9001-KP7L9 Sinyal Lambası Çözümleri
Ürün serisi Harmony 9001K Ürün ya da bileşen tipi Pilot ışığı Ürün grubu 9001K
Schneider XB5-S1B2M12 Biometrik Buton Çözümleri
Ürün ya da bileşen tipi Biometrik anahtar ürüne özel uygulama Malzemelerin ambalajlanması Endastriyel makineler Ürün grubu XB5S şev malzemesi Koyu
Schneider XB5-S2B2M12 Biometrik Buton Çözümleri
Ürün ya da bileşen tipi Biometrik anahtar ürüne özel uygulama Endastriyel makineler Malzemelerin ambalajlanması Ürün grubu XB5S şev malzemesi Koyu
Schneider 9001-KP35LRR9 Sinyal Lambası Çözümleri
range of product Harmony 9001K product or component type Pilot light device short name 9001K
Schneider XD5-PA22 Joystik Kontrol Çözümleri
Ürün serisi Harmony XB5 Ürün ya da bileşen tipi Kumanda kontrolörü Ürün grubu XD5 şev malzemesi Plastik sabitleme bileziği malzemesi
Schneider XB5-S1B2L2 Biometrik Buton Çözümleri
Ürün ya da bileşen tipi Biometrik anahtar ürüne özel uygulama Endastriyel makineler Malzemelerin ambalajlanması Ürün grubu XB5S şev malzemesi Koyu
Schneider XD4-PA22 Joystik Kontrol Çözümleri
Ürün serisi Harmony XDA Ürün ya da bileşen tipi Kumanda kontrolörü Ürün grubu XD4 şev malzemesi Krom kaplı metal sabitleme