range |
TeSys
|
|
---|---|---|
product name |
TeSys GV4
|
|
device short name |
GV4L
|
|
product or component type |
Circuit breaker
|
|
device application |
Motor protection
|
|
poles description |
3P
|
|
utilisation category |
Category A
|
|
trip unit technology |
Magnetic
Electronic |
|
protection type |
Short-circuit
|
|
[In] rated current |
12.5 A
|
|
breaking capacity |
Icu 100 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
Icu 50 kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2 Icu 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 Icu 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 Icu 8 kA at 660…690 V AC 50/60 Hz conforming to IEC 60947-2 Icu 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
|
[Ics] rated service breaking capacity |
100 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 2 kA at 660…690 V AC 50/60 Hz conforming to IEC 60947-2 |
|
Magnetic setting range |
75…175 A
|
|
control type |
Toggle
|